For certain applications, the most
cost-effective solution for poor power factor, excessive voltage distortion,
and IEEE Std 519-1992 violations is to install one or more larger harmonic
filters at a distribution bus or busses.
Generally, an automatic harmonic filter
bank will be installed on the secondary of each main transformer in the plant
requiring power factor and harmonic compensation. Placement of multiple banks
on a common low-voltage system can create problems by changing network harmonic
flows and thereby increase the potential for overloading some of the filter
banks.
Therefore, this practice is not generally
recommended. Where power factor correction is most important, systems tuned to
the 2nd harmonic or below can generally be safely applied in this manner.
Parallel resonance at the 3rd harmonic must be carefully evaluated.
Caution must be exercised when a harmonic
filter is electrically close to the main and is tuned to the 7th
harmonic or higher. In this case, the potential exists to absorb large amounts
of harmonic current from the utility distribution system.
Harmonic filters should be designed
assuming the distribution system will have up to 3% voltage distortion at the
harmonic nearest the tuning frequency per IEEE Std 519-1992. If the harmonic
filter reactors are not equipped with taps, as is common with low-voltage
filters, a good practice is to over specify the thermal rating so that
additional capacitance may be added to detune the filter in the event a
harmonic overload occurs.
If altering the tuning results in
unacceptable filtering of in-plant harmonics, the utility can generally help to
identify methods for reducing the available harmonic current. Possible
utility-side solutions include the following:
Changing the size or status of capacitor
banks to alter the impedance characteristics of the system
Enforcing IEEE Std 519-1992 limits on
customers with excessive harmonic injection
Circuit reconfiguration to isolate
harmonic injectors
Medium-voltage harmonic filters
During lightly loaded conditions, harmonic
filters that are fixed on the bus can produce an overvoltage condition. The
maximum per-unit voltage rise caused by the harmonic filter can be estimated as
approximately equal to the harmonic filter power system frequency current
(i.e., fundamental current) divided by the system three-phase short-circuit
current at the harmonic filter location (see IEEE Std 1036-1992).
If overvoltage is a concern, an
automatically switched harmonic filter should be considered. Switched harmonic
filter(s) comprise a number of steps, each of which is an individually tuned
harmonic filter.
Reactive current controllers (sometimes
referred to as var controllers) that can switch steps in and out automatically
as system reactive current (i.e., power factor) changes are readily available.
Other switching alternatives include the use of current relays, time-of-day
controllers, voltage controllers, or other sensing devices. Switching times
become more important as the harmonic filter is tuned closer to its rated
frequency.
No comments:
Post a Comment