Delayed autoreclosing may need to be
considered when the upstream protection is provided by electromechanical relays
or fuses and the circuit protection is provided by microprocessor-based relays,
unless the microprocessor-based relays can be set to mimick the reset
characteristic of the electromechanical relays.
Without this time-delay reset feature on
the microprocessor-based relay, it is possible to have the upstream device
operate incorrectly, resulting in an overtrip. As an example of this, the
low-set instantaneous trip on a distribution feeder is eliminated to improve
power quality by eliminating momentary service interruptions.
If an instantaneous autoreclose is used
after a time delayed trip, an additional time margin needs to be used between
the operating times of protective devices in order to maintain coordination of
the feeder overcurrent relays and an upstream electromechanical relay or fuse.
By delaying an upstream protective device
to coordinate with the back-to back operation of the feeder relay, coordination
is maintained with the instantaneous reclose. Delaying the autoreclosing
eliminates this problem by allowing all devices time to rest before the next
fault.
Delayed autoreclosing is used on circuits
that have automatic sectionalizers to allow proper coordination with the
distribution circuit breaker. The time-delay autoreclosing of the distribution
circuit breaker needs to be set to match the programmed time intervals of the
sectionalizer switches to allow successful isolation of the faulted line
section.
Distribution circuits that have
customer-owned generators connected to them present a special problem. In most
cases, it will be necessary to delay autoreclosing to allow the customer
generator to be disconnected before the circuit is re-energized from the
utility source.
Removal of the customer generation is
normally accomplished by the operation of an underfrequency, undervoltage, or
reverse power relay, which tend to have longer tripping times. As the operating
time for these devices may be slower to remove the connected generator than the
relays that detected and cleared the fault, autoreclosing times could need to
be extended to allow these devices to operate or the function be disabled.
No comments:
Post a Comment