An inspection analysis of the physical condition of a
plant’s distribution system can be utilized (hopefully on a continual basis) to
improve plant reliability. The following inspection requires little, if any,
capital investment while providing a favorable increase in reliability:
a) Equipment should be periodically checked for proper
condition, and programs should be initiated for preventive maintenance
procedures as required.
1) Oil in transformers and circuit breakers should be
periodically checked for mineral, carbon, and water content as well as level
and temperature.
2) Molded case circuit breakers should be exercised
periodically (that is, operated “on” to “off” to “on”).
3) Terminals should be tightened. Each terminal should be
inspected for discoloration (overheating), which is generally caused by either
a bad connection or equipment overload. Cabinets, etc., should be checked for
excessive warmth. Remember that circuit breakers and fuses interrupt as a
result of heat in the overload mode.
4) Surge arresters should be checked for their readiness to
operate.
b) Distribution centers should be checked to see that spare
fuses are available. Spare circuit breakers may also be necessary for odd sizes
or special applications.
c) Switches, disconnect switches, bus work, and grounds
should be checked for corrosion, and unintentional entry of water or corrosive
foreign material. It may be wise to operate suspected switches to see that
their mechanisms are free, so that faults can be properly isolated and switches
safely re-fused.
d) The mechanical part of the electrical system should be
checked.
1) The conduit, duct, cable tray, and busway systems should
be well supported mechanically, and the grounding system should be electrically
continuous. Employees can be shocked or injured if a circuit faults to ground
without a solid continuous return path to the source interrupter.
Supports, such as wood poles, should be checked for
excessive rusting or rotting, which would significantly reduce their mechanical
strength.
2) Open wire circuits should be checked for insulator and
surge arrester failure and contamination.
3) The system’s key locations (open area distribution
centers and lines) should be checked for foreign growth, such as trees, weeds,
shrubs, etc., as well as for general accessibility. The distribution centers
should be free from storage of trash, flammables, or even general plant
inventory.
4) Permanent and portable wiring should be checked for
fraying or other loss of insulating value.
5) In general, the system should be checked for any obvious
situations where accidents could precipitate an interruption.
e) The electrical supply room(s) should be thoroughly
checked.
1) The relay and control power fuses should be intact (not
blown).
2) All indicating lights should be operable and clearly
visible.
3) All targets should be reset so that none show a tripping.
Counters (if any) should be checked and the count (number) should be recorded.
4) The control power, batteries, emergency lighting, and
emergency generation should be tested and checked to see that they are
operational. In many cases, plants have been unable to transfer to their spare
circuit or start their standby generator because of dead batteries.
No comments:
Post a Comment