IEC STANDARD APPROACH ON INSULATION COORDINATION BASICS AND TUTORIALS

The detailed procedure for insulation co-ordination set out in IEC 60071-1 (European standard EN60071 1 is identical) consists of the selection of a set of standard withstand voltages which characterize the insulation of the equipment of the system. This set of withstands correspond to each of the different stresses to which the system may be subject:

• Continuous power frequency voltage (the highest voltage of the system for the life of the system).
• Slow-front overvoltage (a standard switching impulse).
• Fast-front overvoltage (a standard lightning impulse).
• Very-fast-front overvoltage (depends on the characteristics of the connected apparatus).
• Longitudinal overvoltage (a voltage between terminals combining a power frequency voltage at one end with a switching (or lightning) impulse at the other).

These voltages and overvoltages need to be determined in amplitude, shape and duration by system study. For each class of overvoltage, the analysis then determines a ‘representative overvoltage’, taking account of the characteristics of the insulation.

The representative overvoltage may be characterized by one of:
• an assumed maximum,
• a set of peak values,
• a complete statistical distribution of peak values.

The next step is the determination of ‘co-ordination withstand’ voltages – the lowest values of the withstand voltages of the insulation in use which meet the system or equipment performance criteria when subjected to the ‘representative overvoltages’ under service conditions. Factors are then applied to compensate for:

• the differences in equipment assembly,
• the dispersion of the quality of the products within the system,
• the quality of installation,
• the ageing of installation during its lifetime,
• atmospheric conditions,
• contingency for other factors.

This results in so-called ‘required withstand voltages’ – test voltages that must be withstood in a standard withstand test. 

In specifying equipment the next step is then to specify a standard test withstand voltage (a set of specific test voltages is provided in IEC 60071-1) which is the next above the required withstand voltage, assuming the same shape of test voltage.

 A test conversion factor must be applied to the required withstand voltage if the test voltage is of a different shape to the class of overvoltage in question.

Related post



No comments:

PREVIOUS ARTICLES
free counters