To better understand how harmonic currents affect
transformers one must first understand the basic construction. For power
transformers up to about 50 MVA, the typical construction is core form. The low-voltage winding is generally placed
next to the core leg, with the high-voltage winding wound concentrically over
the low-voltage winding.
For some high-current transformers, these windings may be
reversed, with the low-voltage winding wound on the outside over the
high-voltage coil. The core and coils are held together with core clamps, and
the core and coil is generally enclosed by a tank or enclosure.
Losses in the transformer can be broken down into core loss,
no-load loss, and load loss. Load losses can be further broken down into I^2R
loss and stray loss. Stray loss can be further broken down into eddy current
losses and other stray losses.
Electromagnetic fields from the ac currents produce voltages
across conductors, causing eddy currents to flow in them. This increases the
conductor loss and operating temperature. Other stray losses are due to losses
in structures other than the windings, such as core clamps and tank or
enclosure walls.
The region of maximum eddy-current losses is the upper
region of the winding, near the high–low barrier. The same usually exists at
the bottom of the transformer winding as well, but it is typically the upper
region that has the most damaging effects, as it is in a higher ambient
temperature of liquid or air. Core-loss components can be broken down into core
eddy loss, hysteresis loss, and winding-excitation loss.
These losses are a function of the grade of core steel, the
lamination thickness, the type of core and joint, the operating frequency, the
destruction factor during manufacture, and the core induction. Harmonic
currents can create harmonic voltage distortions and somewhat increase the core
loss, the exciting current, and sound levels while leading to potential
core-saturation problems.
However, this is not considered to be the main cause of problems
in rectifier transformers. ANSI/IEEE C57.18.10 does not calculate any effect on
the core loss by the harmonic currents.
Other stray losses are generally proportional to the current
squared times the harmonic frequency order to the 0.8 power, as shown earlier
in Equation 2.4.2. Metallic parts will increase in temperature, and load loss
will increase.
These losses are generally not detrimental to the life of
the transformer as long as the insulating system is not damaged. The metallic
parts typically affected are the core clamps, winding clamping structures, and
tank or enclosure walls.
The use of nonmagnetic materials, magnetic shields,
conductive shields, increased magnetic clearances, and interleaving of
high-current buswork are useful methods in reducing the stray losses that are
amplified by the harmonic currents.
The transformer designer must make efforts to reduce the
winding eddycurrent losses due to the harmonic amplification of these losses.
Careful winding and impedance balances, dimensioning of the conductors, and
transposition of the conductors are useful methods in this effort.
No comments:
Post a Comment