COLD LOAD PICK UP FAULT CONSIDERATIONS BASICS AND TUTORIAL

Cold load pickup, occurring as the result of a permanent fault and long outage, is often maligned as the cause of many protective device misoperations. Figure shown below, illustrates several cold load pickup curves developed by various sources. These curves are normally considered to be composed of the following three components:



1) Inrush – lasting a few cycles
2) Motor starting – lasting a few seconds
3) Loss of diversity – lasting many minutes.

When a lateral fuse misoperates, it is probably  not the result of this loss of diversity, i.e., the fuse is overloaded. This condition is rare on most laterals. Relay operation during cold load pickup is generally the result of a trip of the instantaneous unit and probably results from high inrush.

Likewise, an FCI operation would not appear to be the result of loss of diversity but rather the high inrush currents. Since inrush occurs during all energization and not just as a result of cold load pickup, it can be concluded that cold load pickup is not a major factor in the application of Fcls.

Related post



No comments:

PREVIOUS ARTICLES
free counters