The Y-Y transformer connection was poorly understood in the
early days of power engineering and it received a very bad reputation when it
was first used; in fact, this connection was avoided for a long time until its
limitations were overcome by good engineering practice.
Some of the inherent disadvantages of the Y-Y connection are
discussed below:
1. The presence of third (and other zero-sequence) harmonics
at an ungrounded neutral can cause overvoltage conditions at light load. When
constructing a Y-Y transformer using single-phase transformers connected in a
bank, the measured line-to-neutral voltages are not 57.7% of the system
phase-to-phase voltage at no load but are about 68% and diminish very rapidly
as the bank is loaded.
The effective values of voltages at different frequencies
combine by taking the square root of the sum of the voltages squared. With
sinusoidal phase-to-phase voltage, the third-harmonic component of the
phase-to-neutral voltage is about 60%, so the effective voltage across the
winding is calculated as follows:
E = [0.577^2 + (0.6*0.577)^2]^1/2 = 68%
2. There can be a large voltage drop for unbalanced
phase-to-neutral loads. This is caused by the fact that phase-to-phase loads
cause a voltage drop through the leakage reactance of the transformer whereas
phase-to-neutral loads cause a voltage drop through the magnetizing reactance,
which is 100 to 1000 times larger than the leakage reactance.
3. Under certain circumstances, a Y-Y connected three-phase
trans-former can produce severe tank overheating that can quickly destroy the
transformer. This usually occurs with an open phase on the primary circuit and
load on the secondary.
4. Series resonance between the third harmonic magnetizing
reactance of the transformer and line to-ground capacitance can result in
severe overvoltages.
5. If a phase-to-ground fault occurs on the primary circuit
with the primary neutral grounded, then the phase-to-neutral voltage on the
unfaulted phases increases to 173% of the normal voltage. This would almost
certainly result in overexcitation of the core, with greatly increased
magnetizing currents and core losses.
6. If the neutrals of the primary and secondary are both
brought out, then a phase-to-ground fault on the secondary circuit causes
neutral fault current to flow in the primary circuit. Ground protection
relaying in the neutral of the primary circuit may then operate for faults on
the secondary circuit.
The obvious remedy for some of the disadvantages of the Y-Y
transformer connection would be to simply solidly ground both the primary and
secondary neutrals. In fact, this is standard practice for virtually all Y-Y
transformers in systems designed by utility companies.
No comments:
Post a Comment